Product Description: The key facilities of the data center are power distribution and air conditioning systems, and the comprehensive test is the load test of key facilities. The IT equipment is gradually installed after the data center is delivered for use, that is, there is no it load in the data center during construction acceptance, so many problems of key facilities cannot be exposed. Therefore, false load arises at the historic moment. Simulate the actual operation and heating of IT equipment through dummy load to ensure the effective operation of data center power supply and company system (including UPS system), air conditioning fresh air system, lightning protection and grounding system, monitoring system and other systems, and timely find and solve problems through testing, so as to eliminate potential safety hazards. Product importance: Fake load verification test, as a comprehensive inspection and test before the new data center is put into operation, has been recognized and supported by more and more people in the industry. And as an indispensable key project link in the new data center project. The introduction of this link plays a very important role in the project, operation and data center life cycle management. It can eliminate hidden dangers in advance, establish operation and maintenance procedures and carry out operation drills. It is also the final guarantee for the overall project delivery quality. At this stage, the hidden dangers buried in design, construction and equipment can be rectified at the least cost, so as to avoid the systematic risk of the project. Application fields: Acceptance of the refrigeration system in the machine room, provision of acceptance report on the air flow environment in the machine room, verification of the design index of the machine room, and acceptance of the power system in the machine room | |
Product name | AC / DC rack type dummy load |
model | WS-890045E |
The main technical indexes and parameters of the load box can be customized according to customer needs | |
Rated voltage | UE = 220V for both AC and DC AC 220VAC DC test DC 270V |
Rated power | 4.5kW |
Maximum current | 20.4A |
Minimum step | 0.5KW |
accuracy | 3% |
control mode | Manual |
Panel layout | power switch |
Power supply socket | C14 power socket |
Load mode | Constant resistance |
Protection function (optional) | Short circuit protection |
Heat dissipation mode | Air cooling |
Working power supply | Input test supply |
Installation mode | Meet the installation specification of 19 inch standard cabinet |
work environment | -10℃~55℃ |
Overall dimension | 4U |
Equipment weight | 15KG |
Appearance color | black |